FTC can cater to clients’ needs in producing security cables which are fire resistant for use in firefighting plants.
Both with special special ceramized Silicon isulation, with or without alluminium foil and with LSZH outer sheath.
These cables are produced to be able to work between 30 and 180 minutes in fire situation.
Reference Standards ( internal cores ):
- CEI 20 - 19 CENELEC HD 22 ( for the insulation )
- CEI 20 - 29 CENELEC HD 383 ( for the conductor )
Certifications tests availables:
- BS 6387CWZ IEC 60331/21 DIN 4102 - 12
- EN 50200:2000-02, EN 50266, EN 50267, WN 50268
![]()
This cable is available from 0,5 to 2,5 sqmm and from 2 to 5 cores.
| Section ( mm2 ) | Max electrical resistance to 20° | Strand and wire diameter | Insulation diam. (mm) | Outer Diameter |
| 2 x 1.00 | 18.01 Ohm/Km | 1 x 1.13 | 2.6 ± 0.1 | 8,2 ± 0.2 |
| 3 x 1.00 | 18.01 Ohm/Km | 1 x 1.13 | 2.6 ± 0.1 | 9,2 ± 0.2 |
| 4 x 1.00 | 18.01 Ohm/Km | 1 x 1.13 | 2.6 ± 0.1 | 10,2 ± 0.2 |
| 2 x 1.50 | 12.01 Ohm/Km | 1 x 1.38 | 2.8 ± 0.1 | 8,6 ± 0.2 |
| 3 x 1.50 | 12.01 Ohm/Km | 1 x 1.38 | 2.8 ± 0.1 | 9,6 ± 0.2 |
| Section ( mm2 ) | Max electrical resistance to 20° | Strand and wire diameter | Insulation diam. (mm) | Outer diameter |
| 4 x 1.50 | 12.01 Ohm/Km | 1 x 1.38 | 2.8 ± 0.1 | 10,4 ± 0.2 |
| 2 x 2.50 | 7.41 Ohm/Km | 7 x 0,67 | 3.4 ± 0.1 | 10,6 ± 0.2 |
| 3 x 2.50 | 7.41 Ohm/Km | 7 x 0,67 | 3.4 ± 0.1 | 11,6 ± 0.2 |
| 4 x 2.50 | 7.41 Ohm/Km | 7 x 0,67 | 3.4 ± 0.1 | 12,6 ± 0.2 |