This article describes a range of electric power cables and telephone cables available from FCT.
Indoor Telephone Cable
J-YY Single-wired conductor of plain copper wire, PVC-based core insulation, fur cores twisted to star quad, core colours according to VDE 0815, PVC-based outer scheath, RAL 7032 J-Y (ST) Y Like J-YY...BD but cores are twisted in pairs, cable core covered by a static screen of aluminium-clad plastic wire with copper conductor, PVC-based outer sheath RAL 7032.

BMD brandmeldekabel is the same cable but with red PVC sheath, request for alarm system.
Fireproof Cables Eurosafe 180

FTC can cater to clients' needs in producing security cables which are fire resistant for use in firefighting plants, both with special special ceramised Silicon isulation, with or without alluminium foil and with LSZH outer sheath. These cables are produced to be able to work between 30 and 180 minutes in fire situation. This cable is available from 0,5 to 2,5 sqmm and from 2 to 5 cores
| Section ( mm2 ) | Max electrical resistance to 20° | Strand and wire diameter | Insulation diam. (mm) | Outer diameter |
| 2 x 1.00 | 18.01 Ohm/Km | 1 x 1.13 | 2.6 ± 0.1 | 8,2 ± 0.2 |
| 3 x 1.00 | 18.01 Ohm/Km | 1 x 1.13 | 2.6 ± 0.1 | 9,2 ± 0.2 |
| 4 x 1.00 | 18.01 Ohm/Km | 1 x 1.13 | 2.6 ± 0.1 | 10,2 ± 0.2 |
| 2 x 1.50 | 12.01 Ohm/Km | 1 x 1.38 | 2.8 ± 0.1 | 8,6 ± 0.2 |
| 3 x 1.50 | 12.01 Ohm/Km | 1 x 1.38 | 2.8 ± 0.1 | 9,6 ± 0.2 |
| 4 x 1.50 | 12.01 Ohm/Km | 1 x 1.38 | 2.8 ± 0.1 | 10,4 ± 0.2 |
| 2 x 2.50 | 7.41 Ohm/Km | 7 x 0,67 | 3.4 ± 0.1 | 10,6 ± 0.2 |
| 3 x 2.50 | 7.41 Ohm/Km | 7 x 0,67 | 3.4 ± 0.1 | 11,6 ± 0.2 |
| 4 x 2.50 | 7.41 Ohm/Km | 7 x 0,67 | 3.4 ± 0.1 | 12,6 ± 0.2 |
Data Telephone Fire Resistants Cables Eurosafe E30 / E60
![]()
- Fire resistant EN 1363 -1 Din 4102 -12
- Halogen Free
- Fire retardant ( VDE 0472 Part 804-C, BS 4066 Part 3 (NMV 1,5), IEC 332-3 cat.CF)
- Low smoke and fume
- No emission of corrosive and toxic gases
- VDE 0815
| Conductor Diameter: | - 0,8 mm | 0,6 mm |
| loop resistance: insulation resistance at 20° C max: Nominal capacitance at 800 Hz: Capacitance unbalance between pairs at 800 Hz k1 max: k9 - K12 max: | 130 mm | 73,2 mm 100 M km 120 nF/km 300 pF/500m 100 pF/500m |
| Number of pairs and conductor diam. ( mm ) | Calorific patential kWh/m | Overall diam. approx. mm | Copper weight (mm) | Weight of cable approx. Kg/km |
| 1 x 2 x 0,6 2 x 2 x 0,6 3 x 2 x 0,6 5 x 2 x 0,6 10 x 2 x 0,6 1 x 2 x 0,8 2 x 2 x 0,8 3 x 2 x 0,8 5 x 2 x 0,8 10 x 2 x 0,8 | 0,18 0,30 0,35 0,48 0,74 0,24 0,41 0,50 0,69 0,11 | 6,3 9,0 9,4 11,0 13,6 7,4 10,9 11,5 13,5 17,0 | 14 25 37 59 116 25 45 65 106 206 | 30 35 50 60 70 160 190 240 285 360 |
Power Cables and Special Cables
![]()
FTC can supply the Security Market with a range of complementary cables used in installations.
Available version shielded and unshielded